POWER VENT INSTRUCTIONS
(Refer to installation diagrams)
The POWER VENT must be placed vertically with the label
right side up in order for the backdraft damper to function properly.
Place the POWER VENT higher than the top of the battery
box and indoors, especially in cold climates.
Use no more than four 90º bends including one at the exterior
terminus facing down. Put a screen on the outside pipe terminus
to keep insects and debris out. If installed in a dusty or construction
environment put a porous foam or paper filter on the battery box inlet.
DO NOT glue the Power Vents in place. Friction fit is adequate. DO NOT
drip glue onto the fan blades.
Use 2" PVC dwv pipe on 12 and 24 volt systems. Use 2"
intake and 3" output PVC dwv pipe on 48 volt systems.
Place a 1 amp fuse (included) at the start of the positive circuit
wire. Thermostat wire and phone splice/tap connectors (ULG or UG)) work
well to connect the Power Vent. Use a cable tie around the base of the
Power Vent and wires to provide strain relief and create a neat wire job
A controller is usually used in the circuit to cycle the fan .
OutBack inverters and charge controllers may have a 12 volt powered
auxiliary relay available. Other inverters may or may not have a voltage
controlled auxiliary relay. Please refer to the appropriate manual for
hook up and programming instructions. If no relay is available,
a Solar Converters Simple Switch (model VCS1AH) may be used. (also check this
websites faq's). The voltage set points
for turning the fan on and off are above the full state of charge
voltage of the battery but below the battery gassing voltage.
In the case of grid tied systems where the batteries are kept
at float voltage 24 hours/day it may be necessary to run the
fan full time as the batteries are always gassing. An alternative is to
remove the backdraft damper to allow passive venting and only switch fan
on when batteries are above float voltage.
For the inquisitive, please note that the 48 volt Power Vents are
built with two 24 volt fans wired in series.
SET POINTS FOR FLOODED LEAD ACID BATTERIES
| SYSTEM VOLTAGE |
FAN ON SET POINT |
FAN OFF SET POINT |
HYSTERESIS
(Trace inverters) |
| 12 |
13.2 VOLTS |
13.0 VOLTS |
0.2 |
| 24 |
26.4 VOLTS |
26.1 VOLTS |
0.3 |
| 48 |
52.8 VOLTS |
52.2 VOLTS |
0.6 |
LIMITATIONS AND DISCLAIMER.
This vent only moves a small volume of air. It is designed for
home systems with typical charging capabilities of 150 DC amps
or less. Hydrogen gas creates an explosion risk at concentrations
of only 4%. Make sure vent openings are free and clear including
safety vent hole at the bottom of the POWER VENT. Periodically
check to make sure fan is running during charge periods. Keep
your batteries and connections clean and tight.
During equalization charges on large systems provide additional
ventilation.
Having no control over the use or installation of this product,
we assume no liability connected with its' use. The Power Vent
itself is warrantied for 2 years if installed in accordance with
these instructions.